Analog Output Fault Action - Omron GX-ID1611 User Manual

Gx-series, ethercat remote i/o terminal ethercat slave units
Table of Contents

Advertisement

8 Analog I/O Slave Unit
8-5-2

Analog Output Fault Action

Overview of functions
 Purpose
This function outputs set values if a communications error occurs.
 Details of functions
It is possible to set a value to be output when a communications error occurs for each point.
Select an output value from the following 5 patterns.
Output pattern
Hold Last State
Low Limit
High Limit
User Count
Zero Count
(Default setting)
• Output value corresponding to the output range and output pattern
Output range
0 to 5 V
1 to 5 V
0 to 10 V
−10 to +10 V
4 to 20 mA
Setting method
Set by SDO communications.
The target index is 3240 hex.
For the set values, refer to the information in the corresponding index of "Appendix A-1 Object
Dictionary" in Page A - 48.
8 - 16
Holds and outputs the value immediately before the error occurred.
Outputs the values in the following table according to the output
range.
Outputs the values in the following table according to the output
range.
Outputs the value specified by users.
hex
Outputs the 0000
values of each output range.
Hold Last
Low
State
Limit
−0.25 V
5.25 V
0.8 V
5.2 V
−0.5 V
Hold
10.5 V
−11 V
11 V
3.2 mA
20.8 mA
Contents
High
User Count
Limit
Specified value by a user
from −0.25 to 5.25 V
Specified value by a user
from 0.8 to 5.2 V
Specified value by a user
from −0.5 to 10.5 V
Specified value by a user
from −11 to 11 V
Specified value by a user
from 3.2 to 20.8 mA
GX-series EtherCAT Slave Unit User's Manual
Zero
Count
0 V
1 V
0 V
0 V
4 mA