Event name
Non-volatile Memory Hardware Error
Meaning
An error occurred in non-volatile memory.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
LED
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Non-volatile memory failure.
Attached
None
information
Precautions/
The emergency error code is 5530 hex.
Remarks

12-1-5 Emergency Error Code

The table below shows types of emergency error codes used in GX-series EtherCAT Slave Units and
corresponding error contents.
Error codes common to GX-series EtherCAT Slave Units
Error
Name of error
code
Non-volatile
5530 hex
Memory
Hardware Error
Slave Unit
6140 hex
Verification
Error
GX-series EtherCAT Slave Unit User's Manual
Source details
Observation
Recovery
Continues
Operation
EtherCAT NET ERR
---
Data type
---
Correction
Replace the EtherCAT Slave Unit.
Contents
A timeout was
detected when writing
data to non-volatile
memory during
EtherCAT
communications.
At turning ON the
power supply, a
verification error
occurred on the Slave
Unit information stored
in the Slave Unit.
12 Troubleshooting and Maintenance
Event code
04A10000 hex
Slave
Detection
timing
---
Log category
Writing to non-volatile memory is not possible.
EtherCAT LINK/ACT
---
Name
---
Prevention
None
Notification to
Diagnosis
EtherCAT
history
Master Unit
Not
Can be notified
saved
Cannot be
Saved
notified
When
establishing
communications
after turning ON
power to the
Slave Unit
System
Measures
Write the data again.
If the error occurs
even after restarting
the power supply, the
Slave Unit is
damaged. Replace the
Slave Unit.
12 - 19