7-4-13 e-CON Connector Type 16-point Input and 16-point Output Slave Unit
GX-MD3218/MD3228
Specification
Common to input section and output section
Item
Internal I/O common
I/O indicators
Unit power supply current
consumption
e-CON connector
insertion durability
Weight
Expansion functions
Short-circuit protection
function
Input section
Item
Input capacity
ON voltage
OFF voltage
OFF current
Input current
ON delay
OFF delay
Input filter value
Number of circuits per
common
Isolation method
I/O power supply method
Input device supply
current
I/O power supply current
consumption
GX-series EtherCAT Slave Unit User's Manual
GX-MD3218
NPN
LED display (yellow)
150 mA max. (for 20.4 to 26.4-VDC power supply voltage)
50 times
220 g max.
No
Available at input section only (Operates at 50 mA/point min.)
GX-MD3218
16 points
15 VDC min. (between each input
terminal and the V terminal)
5 VDC max. (between each input
terminal and the V terminal)
1.0 mA max.
6.0 mA max./input (at 24-VDC)
3.0 mA max./input (at 17-VDC)
0.1 ms max.
0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
(Default setting: 1 ms)
16 points/common
No-isolation
Supplied from unit power supply
100 mA/point
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
7 Digital I/O Slave Unit
Specification
GX-MD3228
PNP
Specification
GX-MD3228
15 VDC min. (between each input
terminal and the G terminal)
5 VDC max. (between each input
terminal and the G terminal)
7