3-Tier Terminal Block Type 16-Point Input Slave Unit Gx-Id1612/Id1622 - Omron GX-ID1611 User Manual

Gx-series, ethercat remote i/o terminal ethercat slave units
Table of Contents

Advertisement

7 Digital I/O Slave Unit
7-4-5
3-tier Terminal Block Type 16-point Input Slave Unit
GX-ID1612/ID1622
Specification
Item
Input capacity
Internal I/O common
ON voltage
OFF voltage
OFF current
Input current
ON delay
OFF delay
Input filter value
Number of circuits per
common
Input indicators
Isolation method
I/O power supply method
Input device supply
current
Unit power supply current
consumption
I/O power supply current
consumption
Weight
Expansion functions
Short-circuit protection
function
Notes
For the I/O power supply current value to V and G terminals ,refer to "A-5 I/O Power Supply Current" in
Page A - 79.
7 - 28
GX-ID1612
16 points
NPN
15 VDC min. (between each input
terminal and the V terminal)
5 VDC max. (between each input
terminal and the V terminal)
1.0 mA max.
6.0 mA max./input (at 24-VDC)
3.0 mA max./input (at 17-VDC)
0.1 ms max.
0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
(Default setting: 1 ms)
8 points/common
LED display (yellow)
Photocoupler isolation
Supply by I/O power supply
100 mA/point
90 mA max. (for 20.4 to 26.4-VDC power supply voltage)
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
370 g max.
No
No
Specification
GX-ID1622
PNP
15 VDC min. (between each input
terminal and the G terminal)
5 VDC max. (between each input
terminal and the G terminal)
GX-series EtherCAT Slave Unit User's Manual

Hide quick links: