Thermistor Input Interface - Mitsubishi M80 series Connection And Set Up Manual

Hide thumbs Also See for M80 series:
Table of Contents

Advertisement

M800S/M80 Series Connection and Setup Manual
17 Setting the Hardware

17.6.5 Thermistor Input Interface

(1) By connecting the remote I/O unit with thermistor, up to 12 points of thermistor input are available.
For details on the unit which has thermistor input function, refer to "General Specifications: Remote I/O Unit".
(2) Up to 12 points of thermistor are detected in the ascending order of the channel No. and station No. of the remote I/
O unit. The file registers which output the temperature information are assigned to the inputs (thermistor input n
(TIn)), but are not assigned to the 13th or later thermistor input. The relationship between thermistor inputs and file
registers is as follows:
[PLC input signal]
Through the interface you can read the temperature sensed by a thermistor connected to the designated connector
of thermistor input-equipped remote I/O unit.
Channel
TI0
TI1
TI2
TI3
TI4
TI5
TI6
TI7
TI8
TI9
TI10
TI11
File register
ZR13028
ZR13029
ZR13030
ZR13031
The thermistor voltage acquired with the thermistor input-equipped
ZR13032
remote I/O unit is input after converted to a temperature value per
ZR13033
PLC medium-speed cycle.
ZR13034
One station of remote I/O has 4 thermistor inputs, thus 4 PLC
ZR13035
medium-speed cycles are required for the inputs of one station.
ZR13036
ZR13037
ZR13038
ZR13039
343
Data update cycle
IB-1501269-F