4 General Specifications
(Note 2) When the rush current exceeds the maximum output current, always connect a protective
Source output
(Note 3) Always keep the total sum of output current of each Y00 to Y07, Y08 to Y0F, Y10 to Y17, Y18
Y 00
Y 01
Y 02
Y 03
Y 04
Y 05
Y 06
Y 07
Y 08
Y 09
Y 0A
Y 0B
Y 0C
Y 0D
Y 0E
Y 0F
CAUTION
1. When using an inductive load such as a relay, always connect a diode in parallel to the load to prevent a
counter-electromotive force.
2. When the rush current exceeds the maximum output current, always connect a protective resistor serially to
the load to suppress rush currents.
IB-1501269-F
resistor (R=150Ω) serially to the load to suppress rush currents. Make sure that the current is
less than the maximum output current including the momentary current.
24VDC
Load Resistor
Y
to Y1F, Y20 to Y27, and Y28 to Y2F less than 0.8A.
0.2A or less per point
Y10
Y11
Y12
Y13
Total 0.8A
Y14
or less
Y15
Y16
Y17
Y18
Y19
Y1A
Y1B
Total 0.8A
Y1C
or less
Y1D
Y1E
Y1F
Total 3.2A or less
Control
circuit
Y 20
Y 21
Y 22
Y 23
Total 0.8A
Y 24
or less
Y 25
Y 26
Y 27
Y 28
Y 29
Y 2A
Y 2B
Total 0.8A
Y 2C
or less
Y 2D
Y 2E
Y 2F
90