2.2 Types, Measured Ranges and Data Resolutions of Usable Input Sensors
Input
K
J
T
S
R
Thermocouple
N
E
B
PL II
W5Re/W26Re
Micro voltage
Voltage
Current

2.3 Indicated Accuracy for Ambient Temperature

(1) Ambient temperature 23 2°C
Item
K,J,T,E,PL II
S,R,N,
Thermocouple
W5Re/W26Re
B
Micro voltage
Voltage
Current
Input range
-200 to 1372°C
-200 to 1200°C
-200 to 400°C
-50 to 1768°C
-50 to 1768°C
0 to 1300°C
-200 to 1000°C
0 to 1800°C
0 to 1390°C
0 to 2300°C
0 to 10mV
0 to 100mV
-10 to 10mV
-10000 to 10000
-100 to 100mV
0 to 1V
1 to 5V
0 to 5V
0 to 10V
-1 to 1V
-5 to 5V
-10000 to 10000
-10 to 10V
4 to 20mA
0 to 20mA
Less than -100°C
-100 to less than 500°C
500°C or more
-50 to less than 1000°C
1000°C or more
Less than 400°C
400 to less than 1000°C
1000°C or more
Full-scale×( 0.1%)
3
Digital value
-2000 to 13720
-2000 to 12000
-2000 to 4000
-500 to 17680
-500 to 17680
0 to 13000
-2000 to 10000
0 to 18000
0 to 13900
0 to 23000
0 to 20000
0 to 20000
0 to 20000
Error
1.0°C
(indicated value×(0.1%)+1digit)
1.0°C
(indicated value×(0.1%)+1digit)
70.0°C
1.0°C
(indicated value×(0.1%)+1digit)
Data resolution
0.1°C
0.5 V
5 V
1 V
10 V
0.05mV
0.2mV
0.25mV
0.5mV
0.1mV
0.5mV
1mV
0.8 A
1 A
0.5°C

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-q q62hlc-u-hw

Table of Contents