Parameters
4.5 Inputs
4.5.2

Basic unit inputs

Description
SIMOCODE pro has a "BU Inputs" function block with four binary inputs connected to
common potential. You can connect, for example, the buttons for a local control station to the
inputs. These signals can be further processed in SIMOCODE pro by internally connecting
the sockets of the "BU Inputs" function block.
The "BU Inputs" function block consists of:
● Input terminals
"BU Input 1" to "BU Input 4"
● Sockets in SIMOCODE pro that can be connected to any plugs, e.g. to the "Control
Stations" function block
● A socket for the "TEST / RESET" button:
The function of the "TEST / RESET" button is generally dependent upon the operating
state of the device:
– Reset function for the acknowledgement of pending faults
– Test function for carrying out device tests
In addition, other functions can be assigned to the "TEST / RESET" button (e.g. operation of
the memory module and of the addressing plug).
See also Chapter Test / Reset (Page 204).
There is 1 "BU Inputs" function block.
Schematic
The following schematic shows the "BU Inputs" function block:
Figure 4-60
184
located on the outside of the basic unit, corresponding to the sockets
Schematic of the "BU Inputs" function block
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001