Parameters
4.3 Monitoring functions
Response to warning level
Here you can set how SIMOCODE pro should respond if the warning level is undershot. See
also "Tables of responses of SIMOCODE pro" in Chapter Important information (Page 7).
Table 4- 39
Response
disabled
signaling
warn
tripping
delay
Hysteresis for voltage, cos phi, power
Here you can set the hysteresis for voltage, cos phi and power.
Hysteresis for voltage, cos phi, power
142
"Warning level" response for voltage monitoring
Warning level
X (d)
X
X
—
0 to 25.5 s (default: 0.5 s)
0 to 15% of the level value in steps of 1%
(default: 5 %)
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
SIMOCODE pro - Parameterize