Parameters
4.3 Monitoring functions
SIMOCODE pro supports two-phase monitoring of the analog signals of a transducer
(standardized 0/4-20 mA output signal). The analog signals are routed via the analog module
to the 0/4-20 mA (AM1) and 0/4-20 mA (AM2) monitoring function blocks (AM2 only in
conjunction with the SIMOCODE pro V PN and pro V EtherNet IP basic units).
Trip level, warning level
With 0/4-20 mA monitoring, you can parameterize two different response levels (trip level /
warning level) for the upper and lower limits.
Trip level
• 0/4 to 20 > (upper limit)
• 0/4 to 20 < (lower limit)
Warning level
• 0/4 to 20 > (upper limit)
• 0/4 to 20 < (lower limit)
Trip level activity, warning level
Here you can specify in which motor operating states the trip level / warning level will be
active:
• Always (on)
• Always, except TPF (on+)
• If motor is on, except TPF (run)
• If motor is on except TPF, with
startup override (run+)
148
0.0 / 4.0 to 23.6 mA (default: 0.0 / 4.0 mA)
0.0 / 4.0 to 23.6 mA (default: 0.0 / 4.0 mA)
Trip level / warning level is always active, regardless
of whether the motor is running or at a standstill
Trip level / warning level is always active regardless of
whether the motor is running or at a standstill, with the
exception of "TPF," i.e. motor feeder is in the test
position
Trip level / warning level only active if the motor is ON
and not in the test position
Trip level / warning level is only active when the motor
is running, the startup procedure has been completed,
and no test position (TPF) is detected
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
SIMOCODE pro - Parameterize