Note
Type of tripping characteristic
If a 1st generation 3UF711*-1AA00-0 current / voltage measuring module is configured in a
parameterization, but a 2nd generation 3UF711*-1AA01-0 current / voltage measuring
module is used, the tripping characteristic remains that of the 1st generation current / voltage
measuring module.
Merely replacing the measuring module hardware does not change the tripping behavior.
Note
Tripping characteristics
The latest tripping characteristics for SIMOCODE pro can be found in Industry Online
Support (Tripping characteristics 3UF7
(https://support.industry.siemens.com/cs/search?search=3UF7&type=Characteristic&lc=en-
WW)).
Response to overload
The SIMOCODE pro response to overload can be additionally adjusted here.
Further information: See also "Tables of responses of SIMOCODE pro" in Chapter Important
information (Page 7) and Table "Responses" in Chapter Motor protection functions
(Page 31).
Note
With motors for EEx e applications, the response must remain set to "Tripping"!
Cooling-down period
The cooling down period is the amount of time that must elapse before an overload trip can
be reset. This is usually 5 minutes. The thermal memory (motor model – see below) is
deleted after the cooling down period elapses. Supply voltage failures of SIMOCODE pro
during this time extend the specified time correspondingly.
Range:
Cooling down period:
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
60 to 6553.5 s (default setting: 300 s).
Parameters
4.1 Motor protection