Settings
Table 4- 47
Temperature
Trip level T >
Response to trip level T >
Marking for trip level T >
Warning level T >
Response to warning level T >
Marking warning level T >
Hysteresis
Trip level activity, warning level
The trip level / warning level is always active, independent of whether the motor is running or
not (operating state "ON").
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
"Temperature monitoring" settings
Description
-273° - 65262°C (default: -273°)
Setting of response when the temperature is overshot (see the
following table and Chapter Important information (Page 7))
No parameters. Optional marking for identifying the message,
e.g. "Temperature>"; range: Maximum 10 characters
-273° - 65262°C (default: -273°)
Setting of response when the temperature is overshot (see the
following table and Chapter Important information (Page 7))
No parameters. Optional marking for identifying the message,
e.g. "Temperature>"; range: maximum 10 characters.
0° to 255°C in steps of 1°C (default: 5°C)