Parameters
4.2 Motor control
Making internal assignments
You have to make the following assignments:
1. Assign the QE1 contactor control to the relay output which controls the coil of the line
contactor (right).
2. Assign the QE2 contactor control to the relay output which controls the coil of the line
contactor (left).
3. Assign the QE4 contactor control to any relay output from which the "ON input" of the soft
starter should be controlled.
4. Assign the QE3 contactor control to the relay output that supplies the 20 ms
acknowledgment signal to the soft starter.
5. Assign the "ON >", "ON <" and "OFF" control commands to the enabled control
commands.
6. Assign the SIMOCODE pro input to which the "Fault" signal output of the soft starter is
connected to the input (socket) of the standard function "External fault 1."
7. The "startup end" signal of the soft starter can also be wired to one of the inputs and
processed by SIMOCODE pro.
Note
An additional digital module may be necessary for this control function.
116
SIMOCODE pro - Parameterize