Siemens SIMOCODE pro Operating Manual page 133

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Active status of trip and warning levels
Unless deactivated, this function is always active, independent of whether the motor is
running or not (operating state "ON").
Here you can specify in which motor operating states the trip level / warning level will be
active:
• Always (on)
• If motor runs, except TPF (run)
• when the motor is on, except TPF,
with startup override (run+)
Response to trip level
Here you can set how SIMOCODE pro should respond if the trip level is overshot.
See also "Tables of responses of SIMOCODE pro" in chapter Important information
(Page 7).
Table 4- 32
Response
signal
warn
tripping
Delay
1) Extension of the residual current transformer delay
Response to warning level
Here you can set how SIMOCODE pro should respond if the warning level is overshot.
See also "Tables of responses of SIMOCODE pro" in chapter Important information
(Page 7).
Table 4- 33
Response
Deactivated
signal
warn
tripping
Delay
1) Extension of the residual current transformer delay
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Response to "trip level" in ground-fault monitoring
Response to "warning level" in ground-fault monitoring
Trip level / warning level is always active, regardless
of whether the motor is running or at a standstill
Trip level / warning level is only active when the
motor is running
Trip level / warning level is only active when the
motor is running and starting has been completed
Trip level
X (d)
X
0 to 25.5 s (default: 0.5 s)
Warning level
X (d)
X
X
0 to 25.5 s (default: 0.1 s)
Parameters
4.3 Monitoring functions
1)
1)
133