Parameters
4.7 Standard functions
"Safety-related tripping" response
Here, you set the SIMOCODE pro response to safety-related tripping via DM-F Local or
DM-F PROFIsafe.
Note
The response of the modules is not influenced by this setting. If the conditions for safety-
related disconnection are met, the enable circuits are always disabled!
Table 4- 81
Response
tripping
disabled
signaling
warn
Note
In the event that the option "DM-F LOCAL / Separate PROFIsafe function from control
function" has been activated under "Motor control > Control function > Operating mode," only
"disabled," "signal," or "warn" can be set as the response, not "tripping."
"Safety-related tripping" reset
Here, you can select manual or automatic acknowledgment of SIMOCODE pro faults caused
by safety-related tripping.
Reset:
226
"Safety-related tripping" response
Safety-related tripping
X (d)
Manual (default), Auto
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
X
X
X