Trip level, warning level
You can parameterize two different response levels (trip level/warning level). If the current of
one or more phases undershoots the response level or the warning level, voltage monitoring
responds.
Trip level:
Warning level:
Active status of trip and warning levels
Here you can specify in which motor operating states the trip level / warning level will be
active:
• Always (on)
• Always, except TPF (on+)
(default)
• If motor runs, except TPF
(run)
1) When using the SIMOCODE pro V PB basic unit (product version *E03* and higher) with
a current/voltage measuring module
Response to trip level
Here you can set how SIMOCODE pro should respond if the trip level is undershot. See also
"Tables of responses of SIMOCODE pro" in Chapter Important information (Page 7).
Table 4- 38
Response
disabled
signaling
warn
tripping
delay
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
0 to 2040 V in steps of 8 V (default: 0)
0 to 2040 V in steps of 8 V (default: 0)
Trip level / warning level is always active, regardless of
1)
whether the motor is running or at a standstill
Trip level / warning level always effective, regardless of
whether the motor is running or at a standstill;
Exception: "TPF", i.e. motor feeder is in test position
Trip level / warning level only active if the motor is ON and
not in the test position
"Trip level" response for voltage monitoring
Trip level
X (d)
X
X
0 to 25.5 s (default: 0.5 s)
Parameters
4.3 Monitoring functions
141