Parameters
4.2 Motor control
Settings
You will find detailed explanations of the settings in Application selection, settings and
definitions of control functions (Page 66).
Table 4- 23
Soft starter settings
Soft starter
OFF
ОN >
FB ON
Non-maintained command mode
Separate fail-safe function from control
function
Load type
Feedback time
Execution time
114
Description
Control command OFF (connection with any socket, usually with "Enabled
control command OFF" socket)
Control command ON (connection with any socket, usually with "Enabled
control command ON >" socket)
Auxiliary control input "Feedback ON" (connection with any socket
usually with socket "Status - current flowing")
Deactivated (default setting)
•
Activated
•
Deactivated (default setting): A safety-related tripping by the DM-F
•
modules also affects the SIMOCODE pro control function, avoiding
additional follow-on fault messages. This setting is selected for
applications where safety-related tripping directly affects the motor
controlled by SIMOCODE pro.
Activated: A safety-related tripping by the DM-F modules does not affect
•
the SIMOCODE pro control function. This setting is selected for
applications where safety-related tripping does not affect the motor
controlled by SIMOCODE pro.
You can choose between:
Motor (default)
•
Resistive load (see Chapter Application selection, settings and definitions
•
of control functions (Page 66))
Range 0 to 25.5 s (default: 0.5 s)
At least ≥ soft run-down time
Range 0 to 6553.5 s (default: 1.0 s)
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
,