Parameters
4.4 Outputs
2) Output of the effective motor current - only part of the motor current range (overload
range)
The motor current ranges from 0 to 8 A. The rated current I
2 A.
The set current in SIMOCODE ES I
the overload range (2 A to 8 A) is to be displayed on an instrument via the analog module
output. In SIMOCODE pro, the present phase currents or the maximum current (current IL_1,
IL_2, IL_3, max. current I_max) are represented as a as a percentage of the parameterized
current setting I
● 2 A motor current corresponds to 100 % of I
● 8 A motor current corresponds to 400 % of I
● The smallest unit for the effective motor current in SIMOCODE pro is 1% (see measured
values data record 94, "Parameterizing SIMOCODE pro" manual)
Figure 4-53
174
s
in accordance with the selected range:
s
Application example: Motor current output - Overload range
N
corresponds to the rated current I
s
s
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
of the motor at nominal load is
(2 A). However, only
N
SIMOCODE pro - Parameterize