Siemens SIMOCODE pro Operating Manual page 149

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Response to trip level 0/4 to 20 mA > (upper limit), 0/4 to 20 mA < (lower limit)
Here, you can define the response of SIMOCODE pro in the event that the monitored
variable overshoots/undershoots the set trip level:
For further information, see also "Tables of responses of SIMOCODE pro" in Chapter
Important information (Page 7).
Table 4- 44
Response
disabled
signaling
warn
tripping
delay
Response to warning level 0/4 to 20 mA > (upper limit), 0/4 to 20 mA < (lower limit)
Here, you can define the response of SIMOCODE pro in the event that the monitored
variable overshoots/undershoots the set warning level:
For further information, see also "Tables of responses of SIMOCODE pro" in Chapter
Important information (Page 7).
Table 4- 45
Response
disabled
signaling
warn
tripping
delay
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
"Trip level" response for 0/4 to 20 mA monitoring
"Warning level" response for 0/4 to 20 mA monitoring
4.3 Monitoring functions
Trip level
X (d)
X
X
0 to 25.5 s (default: 0.5 s)
Warning level
X (d)
X
X
0 to 25.5 s (default: 0.5 s)
Parameters
149

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents