The following applies for the linear motor model:
When the rated motor current (I
87% (1/1.15 x 100%) in a steady state, and 100% at the moment of an overload trip.
Example:
You have operated and switched off a motor with current setting 100% I
You immediately switch the motor back on. This causes an overload trip with 2 x I
● Tripping time in cold state: approximately 40 s (acc. to tripping characteristic)
● Factor for tripping time with preload 100% I
● Reduced tripping time: 0.19 x 40 s = 7.6 s.
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Factors (linear) for trip times at operating temperature for 1st generation current / voltage
measuring modules
Preload as a percentage of the current setting I
0
20
1
0.56
1
0.75
1
0.77
1
0.77
1
0.76
1
0.76
1
0.76
1
0.77
1
0.76
1
0.77
1
0.76
) is at 100%, the value of "Thermal motor model" is
s
s
40
60
0.51
0.44
0.64
0.52
0.64
0.49
0.63
0.47
0.62
0.46
0.62
0.46
0.60
0.45
0.61
0.45
0.61
0.45
0.60
0.45
0.60
0.45
: 0.19 (see Table)
s
Parameters
4.1 Motor protection
80
100
0.34
0.18
0.36
0.16
0.33
0.14
0.30
0.12
0.29
0.12
0.29
0.11
0.29
0.12
0.28
0.11
0.28
0.11
0.28
0.11
0.28
0.12
.
s
, Class 10.
s
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents