Parameters
4.7 Standard functions
Settings of the DIP switches on the DM-F Local
Table 4- 78
Note
The target setting of the DIP switches in the SIMOCODE ES user interface (can be made
using the mouse pointer) is transferred to the basic unit on download but does not affect the
function of the DM-F Local digital module. The desired function is thus saved as soon as the
parameterization has been created.
You must set the effective parameterization via the DIP switches on the front of the DM-
F Local (see table below and/or the manual "SIMOCODE pro Safety fail-safe digital modules
(http://support.automation.siemens.com/WW/view/en/50564852)"). The basic unit compares
the target setting (from the download) with the actual setting on the DM-F Local. If these
differ, "Configuration deviation" is output!
222
Settings of the DIP switches (DM-F Local)
Switch setting
1
2
3
4
5
6
7
8
With /without cross-circuit detection
1 NC + 1 NO evaluation / 2 NC
evaluation
2x 1-channel / 1x 2-channel
Debounce time for sensor inputs
50 ms / 10 ms
Sensor input automatic start /
monitored start
Cascading input automatic start /
monitored start
With / without startup testing
With automatic starting / without
automatic starting after power failure
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001