Safety guidelines
Note
It is recommended that the QE1 and QE2 contactor controls are wired to the relay outputs of
the basic unit. You need at least 1 digital module for this control function.
Note
Spurious tripping can occur if you use the internal ground-fault detection for star-delta
connections. During delta operation, the summation current is non-zero due to harmonics.
Note
If the current measuring module is switched to delta (normal case), a current which is 1/√3
times smaller must be set for the star-delta starter control function.
Example: I
I
= I
s
I
= 100 A x 1/√3 = 57.7 A
s
Current to be set I
Change-over pause
The switching time from star to delta can be extended by the change-over pause. Reason:
For motors with a high ratio between starting current and rated current, the line voltage plus
motor EMF might result in a very high delta starting current if the change-over pause is too
short. The motor EMF decreases if the pause is longer.
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
= 100 A
n
x 1/√3
n
= 57.7 A
s
Parameters
4.2 Motor control