Change-over pause
The "Change-over pause" parameter can be used to delay switching from "FAST" → "SLOW"
to give the motor enough time to run down.
Note
Two current settings must be set for this control function:
• I
• I
Depending on the current range, the current can in many cases be directly measured at both
speeds with a single current transformer. Otherwise you will need two external current
transformers appropriate for the relevant speed (e.g. 3UF18 with a 1 A secondary
transformer rated current), whose secondary cables must lead through the current
measuring module within the range 0.3 to 3 A. The current setting I
converted according to the secondary currents of the external transformers. For more
information, see Chapter Overload protection (Page 34).
Schematic
Figure 4-20
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
1 for the SLOW speed
s
2 for the FAST speed.
s
Schematic of the "Dahlander" control function, "Protection / Control" function block
Parameters
4.2 Motor control
1 or I
2 must be
s
s
91