Set Current Is2 - Siemens SIMOCODE pro Operating Manual

Industrial controls, motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Transformation ratio - active
When using an interposing transformer, or if the main supply cable is looped several times
through the current measuring module or the current / voltage measuring module, you can
enter the transformation ratio of the interposing transformer. Activate the checkbox if you
wish to use this option. The parameterized current setting continues to correspond here to
the actual rated motor current and does not have to be converted.
The transformation ratio is calculated from the ratio between the rated motor current [A] and
the measured current [A] or any multiple of the ratio.
Note
This parameter is only available when using SIMOCODE pro V PB basic unit above
version *E03*.
Transformation ratio - primary
Enter the primary current here, with the "Transformation ratio - active" checkbox activated.
Range: 0 to 8191.875 (default: 0).
Transformation ratio - secondary
Enter the secondary current here, with the "Transformation ratio - active" checkbox
activated. Range: 0 to 15 (default: 0).
4.1.2.3

Set current Is2

Setting ranges for current setting I
Range: Depends on the selected current measuring module or current / voltage measuring
module.
Current setting I
voltage measuring module:
● 0.3 to 3 A (default: 0.3)
● 2.4 to 25 A
● 10 to 100 A
● 20 to 200 A
● 63 to 630 A
Current setting I
● 0.3 to 4 A (default: 0.3)
● 3 to 40 A
● 10 to 115 A
● 20 to 200 A
● 63 to 630 A
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
2
s
2 when using a current measuring module or a 1st generation current /
s
1 when using a 2nd generation current / voltage measuring module:
s
Parameters
4.1 Motor protection
35