Parameters
4.2 Motor control
Lamp controls and status information:
The feeder status feedback is signaled via the status information or the QL lamp controls.
They are all directly dependent on the status of the auxiliary control input "FB ON". The
number of usable lamp controls and status information is directly dependent on the specified
control function.
Feeder status feedback:
● Status information, e.g. "Status ON <": These are transmitted, for example, via bus to the
automation system and signal the status of the feeder there.
● Displays (lamp control) "Display - QLE <": These can, for example, activate a signal lamp
or a pushbutton lamp for status display
Note
If the motor is running in test operation, the QLE ... / QLA lamp outputs show a different
response (e.g. flashing).
● In addition to the status signals, the "QL..." lamp controls additionally indicate the
following:
– Unacknowledged fault (lamp output general fault QLS is flashing)
– Saving change-over command (QLE lamp outputs are flickering)
– Lamp test: All QL outputs are activated for approx. 2 s.
Extended status and fault messages
● Additional status information:
– Start active: If "Motor" is selected as the load type, this signal is present during the
– Interlocking time active: For control functions with a change in the direction of rotation,
– Change-over pause active: For the "Dahlander," "Pole-changing starter," and "Star-
● Additional status information for the "Positioner" or "Solenoid valve" control function:
– Feedback CLOSED (FC)
– Feedback OPEN (FO)
– Torque CLOSED (TC)
– Torque OPEN (TO).
64
start process of the motor for the duration of the specified class time (e.g. 10 s for
Class 10). Exceptions are the "Overload relay" and "Solenoid valve" control functions.
the signal remains present until the specified interlocking time has elapsed.
delta" control functions the signal is present after changeover until the specified time
has elapsed.
These feedback signals specify the present status of the corresponding limit switch
and/or torque switch. The amount of usable status information is directly dependent on
the selected control function.
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001