High Elevation; Gas Line Installation; Pilot Adjustment; Gas Pipe Pressure Testing - Regency CV40E-NG Owners & Installation Manual

City series zero clearance direct vent gas fireplace
Table of Contents

Advertisement

installation
CV40E/CB40E
NG SYSTEM DATA
Min. Supply
5" WC (1.25 kpa)
Pressure
Manifold Pressure
3.8" WC (0.94 kpa)
Oriice Size
#42 DMS
Maximum Input
28,500 Btu/h
(8.33 kW)
Minimum Input
15,500 Btu/h
(4.54 KW)
CV40E/CB40E
LP SYSTEM DATA
Min. Supply Pressure
11" WC (2.73 kpa)
Manifold Pressure
10.5" WC (2.62 kpa)
Oriice Size
#53 DMS
Maximum Input
28,500 Btu/h
(8.35 kW)
Minimum Input
15,500 Btu/h
(4.54 KW)

High Elevation

This unit is approved for altitude 0 to 4500 ft. (CAN1
2.17-M91.

Gas Line Installation

Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or lex connectors use only
approved ittings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and lex connectors are
usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open lame for leak testing.
60
| City Series

Pilot Adjustment

Periodically check the pilot lames. Correct lame
pattern has two strong blue lames: 1 lowing
around the lame sensor and 1 lowing across
the burner (it does not have to be touching the
burner).
Burner
Flame Sensor
Pilot
Note: If you have an incorrect flame
pattern, contact your Regency
dealer for further instructions.
Incorrect lame pattern will have small, probably
yellow lames, not coming into proper contact
with the rear burner or lame sensor.

Gas Pipe Pressure Testing

The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1
Make sure the unit is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide lat screwdriver.
3. Attach manometer to "IN" and/or "OUT" pres-
sure tap(s) using a 5/16" ID hose.
4. Turn the unit on with the remote or wall switch
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits speciied on the safety label.
6. When inished reading manometer, turn off
the unit, disconnect the hose and tighten the
screw (clockwise) with a 1/8" lat screwdriver.
Note: Screw should be snug, but do not over
tighten.

885 S.I.T. Valve Description

1) 6 Stage lame adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
Ignitor
4
3
®
5
6
2
1
7