Memory Areas
Routing Tables (DM 6450 to DM 6499) (See page 243.)
When the use of routing tables is enabled by the software switch setting, the routing tables are stored in these
words. Do not use them for anything else.
CVM1 and CV-series PLCs
Auxiliary Area
Word(s)
Bit(s)
A001
00 to 15
A015
00 to 15
A302
00 to 15
A401
12
A402
03
07
A405
00 to 15
A410
00 to 15
A422
00 to 15
A427
00 to 15
A502
00 to 07
08 to 15
A503 to A510
00 to 15
CPU Bus Unit Restart Bits
Bits A00100 through A00115 can be turned ON to reset CPU Bus Units number #0 through #15, respectively.
The Restart Bits are turned OFF automatically when restarting is completed.
Do not turn these bits ON and OFF in the program; manipulate them from the CVSS.
CPU Bus Service Disable Bits
Bits A01500 through A01515 can be turned ON to stop service to CPU Bus Units numbered #0 through #15,
respectively. Turn the appropriate bit OFF again to resume service to the CPU Bus Unit.
CPU Bus Unit Initializing Flags
Bits A30200 through A30215 turn ON while the corresponding CPU Bus Units (Units #0 through #15, respec-
tively) are initializing.
CPU Bus Error and Unit Flags
Bit A40112 is turned ON when an error occurs during the transmission of data between the CPU Unit and CPU
Bus Units, or a WDT (watchdog timer) error occurs in a CPU Bus Unit. The unit number of the CPU Bus Unit
involved is contained in word A405.
Bits A40500 through A40515 correspond to CPU Bus Units #0 through #15, respectively. When a CPU Bus
Error occurs, the bit corresponding to the unit number of the CPU Bus Unit involved is turned ON.
CPU Bus Unit Setting Error Flag and Unit Number
Bit A40203 is turned ON when the CPU Bus Units actually installed differ from the Units registered in the I/O
table. The unit number of the CPU Bus Unit involved is written to word A427.
Bits A42700 through A42715 correspond to CPU Bus Units #0 through #15, respectively. When a error occurs,
the bit corresponding to the unit number of the CPU Bus Unit involved is turned ON.
CPU Bus Unit Error Flag and Unit Numbers
Bit A40207 is turned ON when a parity error occurs during the transmission of data between the CPU Unit and
CPU Bus Units. The unit number of the CPU Bus Unit involved is written to word A422.
Bits A42200 through A42215 correspond to CPU Bus Units #0 through #15, respectively. When a CPU Bus
Unit Error occurs, the bit corresponding to the unit number of the CPU Bus Unit involved is turned ON.
Function
CPU Bus Unit Restart Bits
CPU Bus Service Disable Bits
CPU Bus Unit Initializing Flags
CPU Bus Error Flag
CPU Bus Unit Setting Error Flag
CPU Bus Unit Error Flag
CPU Bus Unit Error Unit Number
CPU Bus Unit Duplicate Number
CPU Bus Unit Error Unit Number
CPU Bus Unit Setting Error Unit Number
Port #0 to #7 Enabled Flags
Port #0 to #7 Execute Error Flags
Port #0 to #7 Completion Codes (See page 191)
Appendix B
357