Wire-To-Wire Repeater Unit; Baud Rates - Omron C200HW-CLK21 Operation Manual

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Repeater Units
4-6-1

Wire-to-Wire Repeater Unit

Wire-to-Wire
Repeater Unit
CS1W-RPT01
PWR
T/R1
T/R2
BD H
BD L
SL1
SHLD
TER SW
ON
ON
SW1
TER SW
1
BAUD
2
RATE
BD H
BD L
SL2
SHLD
+
DC24V
INPUT
4-6-2

Baud Rates

Terminating Resistance Switch for SL1
Wire-to-Optical
Repeater Unit
OFF
CS1W-RPT02
PWR
ON
T/R1
T/R2
BD H
BD L
SL1
SHLD
TER SW
ON
ON
SW1
1
BAUD
2
RATE
Terminating Resistance Switch for SL2
SL2
OFF
ON
+
DC24V
INPUT
Baud Rate Switch
OFF
ON
OFF
ON
Set the same baud rates for all nodes on the network using pins 1 and 2 of
DIP switch 1 on the front of the Unit.
ON
SW1
1
BAUD
2
RATE
The baud rate is set as shown below. The maximum transmission distance
will change according to the baud rate setting.
Switch
Pin 1
Pin 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Switch
Terminating
resistance
Not connected
Connected
Note The factory default setting is in bold.
Switch
Terminating
resistance
Not connected
Connected
Note The factory default setting is in bold.
Switch
Baud rate
Pin 1
Pin 2
OFF
2 Mbps
OFF
1 Mbps
ON
500 Kbps
ON
Do not set.
Note The factory default setting is in bold.
Baud rate
2 Mbps
1 Mbps
500 Kbps
Do not set.
Section 4-6
Applicable unit
Turn ON when the Repeater
Unit is connected to the end of
the Network or a segment.
Applicable unit
Turn ON when the Repeater
Unit is connected to the end of
the Network or a segment.
Maximum transmission
distance
1 segment
Network
500 m
1.5 km
800 m
2.4 km
1 km
3.0 km
Maximum transmission dis-
tance
1 segment
Network
500 m
1.5 km
800 m
2.4 km
1 km
3.0 km
---
---
103