Error Codes - Omron C200HW-CLK21 Operation Manual

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Error Log
Time Information
Note
9-3-2

Error Codes

Error
Contents
code
0001
PLC watchdog timer error
Hex
0002
PLC service monitor error
Hex
0003
PLC shared RAM error
Hex
0004
CPU Bus Unit ID number error
Hex
0005
Unit number error
Hex
0006
CPU Unit error
Hex
000D
PLC model error
Hex
314
The time is recorded in BCD with one byte each for the year (the rightmost
two digits), month, day, hour, seconds, and minutes of the time the error
occurred.
1. The PLC's time information can be read and used in the Controller Link
Unit. When the time cannot be read from the PLC, all error log times will
but 0. This can occur for PLC startup errors, Unit No. errors, CPU Unit er-
rors, or PLC model errors. When error logs like these are read from the
Controller Link Support Software, they will be dated 0 s, 0 min, 0 hr, 0 day,
0 month, 2000.
2. When replacing the battery for CS/CJ-series PLCs, it will be necessary to
switch the power supply ON and reset the internal clock.
If the internal clock is not reset, time information in the error log will not be
recorded correctly.
3. The time information will be all zeros for CQM1H-series PLCs unless a
Memory Cassette with a clock is mounted in the CPU Unit. The time infor-
mation will be all zeros in the year 2000 if it is read from Support Software.
The following table lists the error codes (in 4-digit hexadecimal) and the con-
tents of the errors.
Detail code
1st byte
2nd byte
00 Hex
00 Hex
Monitor time (unit: ms)
01 Hex:
00 Hex
Cyclic
02 Hex:
Event
04 Hex:
CPU bus link
00 Hex
00 Hex
Unit set
The value
value
recognized
by the CPU
Unit
Bit 11:No relevant Unit in
I/O table.
Bit 12: Hardware test unit
number recognized.
Bit 13: Incorrect unit num-
ber.
Bit 14: Duplicated unit
number.
Not set
Correction
Written to
EEPROM
Replace PLC's CPU
Yes
Unit.
Check operating
Yes
environment.
Check operating
Yes
environment.
Check I/O
Yes
Connecting Cables.
Check the Unit
Yes
number setting. Rec-
reate the I/O table.
Check the Unit num-
Yes
ber settings. Recre-
ate the I/O table.
Refer to 1-2-4 Con-
Yes
troller Link Unit Mod-
els and PLCs and
PLCs and check the
PLC model.
Section 9-3
Applicable
PLC
All
CV, CS/CJ
CV
CV, CS/CJ
CV
CV, CS/CJ
C200HX/HG/
HE