Omron C200HW-CLK21 Operation Manual page 106

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Constructing Networks with Repeater Units
Partial Conversion to Optical Fiber
Terminating
Resistance: ON
Combining T-Branch Wiring (2-stage Repeater) and Partial Optical Fiber
Terminating
resistance: ON
Terminating
Resistance: ON
(Optical fiber cable)
Segment 1
Segment 1
Terminating
resistance: ON
Terminating
resistance: ON
Segment 2
Note When constructing a network using Repeater Units, each segment must sat-
isfy all of the following requirements:
• The total number of Controller Link Units, Support Boards, and Repeater
Units within a single segment must not exceed 32.
• The total cable length of a single segment must not exceed the specified
value. (500 m at 2 Mbps; 800 m at 1 Mbps; and 1 km at 500 Kbps.)
• The maximum number of repeater stages that can be inserted into the
path connecting any two nodes is two.
• The node at each end of a segment (including Repeater Units) must have
terminating resistance turned ON.
• The baud rates within each segment must be set to the same value.
Terminating
Resistance: ON
Segment 2
Repeater Unit
CS1W-RPT02 or
CS1W-RPT03
Terminating
resistance: ON
Terminating
resistance: ON
Section 3-4
Terminating
Resistance: ON
Terminating
resistance: ON
CS1W-RPT01
Repeater Unit
CS1W-RPT02 or
CS1W-RPT03
Repeater Unit
Segment 3
Terminating
resistance: ON
Segment 4
Terminating
resistance: ON
83