Data Links Procedures; Manually Setting Data Links - Omron C200HW-CLK21 Operation Manual

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Data Links Procedures

2-1
Data Links Procedures
2-1-1

Manually Setting Data Links

1,2,3...
32
When the data link mode is set for manual data link table creation, the data
link tables can be input using the Controller Link Support Software or CX-Pro-
grammer. Use the following procedure.
1. Install and wire the Units.
Contents
a. Mount the Units to
the PLCs.
b. Wire the Network.
2. Prepare for communications.
Contents
a. Set the unit num-
ber.
b. Set the node
address.
c. Set the baud rate.
d. Set the operating
level.
e. Set the terminal
resistance
3. Turn ON the power to the PLC.
Contents
Turn ON the power to
the PLC.
4. Connect the Programming Device.
Contents
Connect the Program-
ming Console or Con-
troller Link Support
Software.
5. Create I/O tables.
Contents
Input the I/O tables.
Method
---
All nodes
---
All nodes
Method
Use the front rotary
CS/CJ-series, CVM1,
switches.
and CV-series PLCs
only
Use the front rotary
All nodes
switches.
Use the DIP switch.
All nodes
Use the DIP switch.
C200HX/HG/HE PLCs
only
Use the front switch
All nodes
for CVM1, CV-series,
End nodes on the net-
CS/CJ-series, and
work: ON
CQM1H-series PLCs
All other nodes: OFF
or the bottom switch
for C200HX/HG/HE
PLCs
Method
---
All nodes
Method
Use the special con-
CS/CJ-series, CVM1,
nection cable.
and CV-series PLCs
Method
Use the Support Soft-
CS/CJ-series, CVM1,
ware or Programming
and CV-series PLCs
Console.
only
Section 2-1
Nodes
Page
59
66
Nodes
Page
98
94,98
95, 99
95
96, 99
Nodes
Page
---
Nodes
Page
21
Nodes
Page
---