Controller Status Read - Omron C200HW-CLK21 Operation Manual

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Commands and Responses for Controller Link Units
6-5-5

CONTROLLER STATUS READ

Command Block
Response Block
06
01
Command
Response code
code
Operating status
Parameters
tions Controller version number, and the third represents the Unit version
number.
Wired/Optical (response)
The connection method for the Controller Link Unit (wired or optical ring). The
configuration is as follows:
Bit
Connection type:
0: Wired
1: Optical ring
Node Address (response): The Controller Link Unit's node address is
returned between 01 and 3E Hex (1 to 62).
Unit Address (response): The Unit address set for the Controller Link Unit
(10 Hex + Unit number), is returned in hexadecimal. Even when there is a Unit
number setting error, the Unit address is returned.
Network Address: The Controller Link Unit's network address, as set in the
routing table, is returned in hexadecimal. When the routing table has not been
set, the address becomes 00 Hex.
Reads the Controller Link Unit's controller status.
06
01
Command
code
00
00
00
Status 1
Status 3
Status 5
Status 2
Status 4
Total 6 bytes
Operating status (response): The operating status of the data links as fol-
lows:
00 (Hex): Data links inactive.
01 (Hex): Data links active.
02 (Hex): Local data links not active. (The data links are active in the net-
work, but the local node is not participating.)
Status 1, Status 4, Status 6 (response): Not used by the Controller Link
Unit. Always set to 00 (Hex).
– : Not used
Maximum number of nodes
00: 32 nodes
01: 62 nodes
00
00
Count 1
Count 8
Status 6
Total 8 bytes
Section 6-5
00
8 bytes
Active node list
203