Setting Data Links
Precautions
122
(Data link start word – 1) + Total number of send/receive
words in area 247 (IR Area)
c) Refer to the Controller Link Support Boards Operation Manual
(W307) for information on the Controller Link Support Board.
d) If CX-Net detects an error during the data link table check, trou-
bleshoot the error referring to 9-4 Troubleshooting Error Mes-
sages in CX-Net Data Link Table Check .
C200HX/HG/HE, CS/CJ-series, CVM1, CV-series, and CQM1H-series PLCs
have different-sized memory areas. When data links are manually set, pro-
vided the PLCs are set so as not to receive data in the areas indicated in the
following diagram, the data link setting area is not limited by the small area
size of the PLC.
Example:
C200HX/HG/HE and
CQM1H-series PLCs
235
If the LR Area in the C200HX/HG/HE or CQM1H Series is manually set for a
data link with a CVM1, CV-series or CS/CJ-series PLC, the LR words will be
linked to CIO 1000 to CIO 1063 in the CVM1, CV-series or CS/CJ-series PLC.
CIO 1064 to CIO 1199 cannot be linked with C200HX/HG/HE or CQM1H-
series PLCs in this way.
C200HX/HG/HE and
CQM1H-series PLCs
LR00
to
LR63
63 (LR Area)
5999 (DM Area)
6143 (EM Area)
CVM1 and
CV-series PLCs
0
100
to
335
336
CVM1, CV-series or
CS/CJ-series PLCs
1000
to
1063
1064
to
Cannot be directly linked
with C200HX/HG/HE or
CQM1H words.
1199
Section 5-2
CS/CJ-series PLCs
200
435
436