Omron C200HW-CLK21 Operation Manual page 252

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Response Codes
Main code
05: Routing error
10: Command format
error
11: Parameter error
Sub-
Probable cause
code
01
Destination node address is not set in
the routing table.
02
Routing table isn't registered.
03
Routing table error
04
The maximum number of relay nodes
was exceeded in the command.
01
The command is longer than the max.
permissible length.
02
The command is shorter than min. per-
missible length.
03
The designated number of data items
differs from the actual number.
04
An incorrect command format has
been used.
05
An incorrect header has been used.
(The local node's relay table or relay
node's local network table is wrong.)
01
A correct memory area code has not
been used or Extended DM Area is not
available.
02
The access size specified in the com-
mand is wrong, or the first address is
an odd number.
03
The first address is in an inaccessible
area.
04
The end of specified word range
exceeds the acceptable range.
06
A non-existent program no. has been
specified.
09
The sizes of data items in the com-
mand block are wrong.
0A
The IOM break function cannot be exe-
cuted because it is already being exe-
cuted.
0B
The response block is longer than the
max. permissible length.
0C
An incorrect parameter code has been
specified.
Remedy
Set the destination node address in the
routing table.
Set the source nodes, destination nodes,
and relay nodes in the routing table.
Set the routing table correctly.
Redesign the network or reconsider the
routing table to reduce the number of relay
nodes in the command. Use a CS/CJ-series
CPU Unit with unit Ver. 2.0 or later with CX-
Programmer Ver. 4.0 or later to send com-
mands across three or more network levels.
Check the command format of the com-
mand and set it correctly.
Check the command format of the com-
mand and set it correctly.
Check the number of items and the data,
and make sure that they agree.
Check the command format of the com-
mand and set it correctly.
Set the routing table correctly.
Check the command's memory area code
and set the appropriate code.
Set the correct access size for the com-
mand.
Set a first address that is in an accessible
area.
Check the acceptable limits of the data area
and set the word range within the limits.
Check the data link tables to be sure the
limit to link words has not been exceeded.
Check the program number and be sure
that it is set correctly.
Check the command data and be sure that
the sixes of the data items are correct.
Check the data link tables to be sure all
nodes in the refresh parameters are in the
common link parameters.
Either abort the current IOM break function
processing, or wait until it is completed and
execute the command.
Check the data link tables for node
addresses that have been set twice.
Check the command format and set the
number of items correctly.
Check the command data and reenter it cor-
rectly.
Check the data link table file for corruption.
Section 6-7
229