Specifications and Configurations
Item
Transmission line
Multi-drop
format
Tree
T-Branch Wiring
Repeater Unit
Long-distance Wiring
Repeater Unit
62-node Configuration
Repeater Unit
Installation
Units are not mounted on the PLC, but are attached to DIN Track or screw-mounted.
Weight
126 g
Current consumption 24 V DC at 60 mA max.
Power supply volt-
24 V DC
age
Allowable power
20.4 to 26.4 V DC (24 V DC 15 to 10%)
supply voltage range
Inrush current
2.5 A max. at 24 V DC (5 ms after startup)
Note
Relay Terminal Blocks
20
500 m max.
(at 2 Mbit/s)
500 m max.
(at 2 Mbit/s)
31 nodes max.
31 nodes max.
1. Repeater Units do not use a node address.
2. See Connection Procedure for an explanation of how Repeater Units are
used.
3. The following Power Supply Unit is recommended: OMRON S82K Series
The following Relay Terminal Block can be used to make maintenance easier
by facilitating replacement of the Controller Link Unit after system operation
has begun.
Name
Relay Terminal Block for
Wired Controller Link Units
Specifications
1:1 type
Partial Conversion to Optical
Wire cable
Repeater Unit
Optical cable
113 g (excluding mount-
ing bracket)
24 V DC at 60 mA max.
Model
CJ1W-TB101
on the ends of the network
Section 1-2
1:1 type
Wire cable
Repeater Unit
116 g (excluding mount-
ing bracket)
24 V DC at 70 mA max.
Remarks
Cannot be used on the nodes