Omron C200HW-CLK21 Operation Manual page 219

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Using the Message Service
C200HX/HG/HE PLCs
Execution
condition
00000
25204
31002
31001
31000
31000
25204
Network Instruction Error Flag
31000
25203
(Continued on the next page)
196
The transmission program will run when IR 00000
KEEP(11)
turns ON, provided that the Network Instruction En-
31000
S
abled Flag is ON and the RECV instruction has not
been executed.
R
IR 31000 remains ON while the SEND instruction is
being executed, and it turns OFF when instruction
@MOV(21)
execution has been completed.
#000A
DM 0000
Control Data Preparation
@MOV(21)
DM 0000
#9500
DM 0001
DM 0001
DM 0002
* No destination network address specified
@MOV(21)
** Response required, 5 retries, direct designa-
#0003
tion, monitoring time: default
DM 0002
Beginning Word for Indirect Receiving by
@MOV(21)
Destination Node
#0500
DM 0020
DM 0020
DM 0021
@MOV(21)
#4000
DM 0021
Transfers the 10 words beginning at IR 000 to the 10
@XFER(70)
words beginning at DM 0010.
#0010
000
DM 0010
Transfers the 10 words beginning at DM 0010 of the
@SEND(90)
source node to the words beginning with DM 4000
DM 0010
(specified by DM 0020 and DM0021) at node address 3.
DM 0020
DM 0000
Creates reset input.
DIFU(13) 31001
Turns ON to indicate transmission error.
00200
Section 6-3
0 0
0 A
10 send words*
9 5
0 0
Operating level 1**
0 0
0 3
Node 3, Unit 0 (a PLC)
Beginning word for
0 5
0 0
receiving (by destina-
4 0
0 0
tion node) = DM4000
(05: DM designation)