Operating program
Setting the operating program for ventilation
Extended menu
1.
2. "Ventilation"
3. "Operating program"
4. For example "Ventilation program"
For further possible operating programs, see
page 15.
Ventilation without heat recovery
Further information can be found in chapter
"Terminology" in the appendix.
Setting the room temperature for ventilation
Factory setting: 20 °C
Note
As soon as the room temperature exceeds the set
■
value specified here by more than 1 °C, ventilation
without heat recovery can take place.
Set the room temperature for ventilation up to 4 °C
■
lower than the room temperature for heating/cooling
and "Party mode". This will ensure that the bypass
functions correctly.
Setting a minimum temperature for ventilation
Factory setting: 16 °C
Note
As soon as the temperature of the supplied air
■
exceeds the minimum temperature specified here,
ventilation without heat recovery can take place.
The lower this temperature is set, the greater is the
■
risk of condensation forming on the outside of the
pipework. This condensation can result in building
damage.
Time program
Further information can be found in chapter
"Terminology" in the appendix.
Setting a time program for ventilation
Factory setting: One time phase from 00:00 to 24:00 h
for every day of the week with the operating status
"Standard".
(cont.)
Extended menu
1.
2. "Ventilation"
3. "Set room temperature"
4. / for the required value.
Note
This menu is not available if your heating circuit HC1 is
a ventilation heating circuit.
Advanced menu
1.
2. "Ventilation"
3. "Min supply air t. byp"
4. / for the required value.
Note
We recommend maintaining the factory setting, partic-
ularly if your heating circuit HC1 is a ventilation heating
circuit.
Ventilation
33