Accessing The Error Memory; Automatic Error Code Clearing; Clearing Error Codes - DeDietrich IX 245-130 Installation, User And Service Manual

Floor-standing condensing gas boiler
Table of Contents

Advertisement

Fig.206
12.2

Accessing the error memory

Fig.207
18. February 2014
Tuesday
1.5 bar
MENU
Fig.208
----------------------------------------------------
Information
Information
Set time and date
6"
12.3

Automatic error code clearing

12.4

Clearing error codes

7702684 - v04 - 05092019
3
MW-4000275-2
14:13
MENU
MW-3000052-EN-02
MENU
MENU
MW-3000082-EN-03
3. Clip the HMI back onto its support.
1. Press the
key to access the parameters.
MENU
2. Press the
and
MENU
3. Select the Commissioning menu by turning the
4. Confirm the menu selection by pressing the
Important
Press the
key to return to the main display.
MENU
The list of parameters for the Error mode can now be accessed.
Use the
button to consult them.
5. Select the Error menu by turning the
6. Confirm the menu selection by pressing the
Important
Press the
key to return to the main display.
MENU
For more information, see
List of installer parameters, page 87
If the symbol
is displayed at the same time as the error code, the error
code is automatically cleared when the cause that prompted it stops.
A flow or return temperature in excess of the critical value prompts an
error code. The error code is automatically cleared when the temperature
drops below the critical value.
If the probable cause of an error code is resolved but the error code
continues to be displayed, proceed as follows to clear the error code:
1. Press the
button.
The command Reset? Yes is displayed on the control panel.
keys simultaneously for at least 6 seconds.
button.
button.
button.
12 Troubleshooting
button.
IX