3=Zone Setup; Enable; Disable; Zone 97, 98 And 99 - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Master Programming Level
3.6.3 Zone Setup
PROGRAMMING
Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as illustrated
1=AUTOPROGRAM
below:
2=POINT PROGRAM

3=ZONE SETUP

Programming Screen #2
ZONE SETUP

1=ENABLE

2=DISABLE

3=ZONE 97 98 99
Zone Setup Screen #1
Enable
ZONE SETUP
1=ENABLE
2=DISABLE
Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:
3=ZONE 97 98 99
Zone Setup Screen #1
This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z.
Another zone can then be enabled.
Disable
ZONE SETUP
1=ENABLE
2=DISABLE
Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:
3=ZONE 97 98 99
Zone Setup Screen #1
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be disabled and the cursor will return to the original position next to
the Z. Another zone can then be disabled.

Zone 97, 98 and 99

Pressing 3 for Zone 97, 98 and 99, while viewing Zone Setup Screen #1, will display the following
screen:
Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose
applications. In the above illustration, the three zones are shown Off, which means they can be
programmed to function in the same manner as all other zones, by assigning them to input and
output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the
display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 97 to activate. By
assigning Zone 97 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONE TO ENABLE
Z
Enable Screen
ZONE TO DISABLE
Z
Disable Screen
SPEC PURPOSE ZONE
1=PAS 97
2=PRESIGNAL 98
3=TWO STAGE 99
Zone 97, 98 and 99 Screen
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
OFF
OFF
OFF
Programming
87