Optional Module Installation
ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.24. After the
ANN-I/O is connected to the panel, it must be added to the system via FACP programming. Refer
to the section titled "ANN-I/O Options" on page 108.
ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized so
that there is approximately 10 mA of current for each LED. No series resistors are required. LED
outputs can be mapped to output circuits. Refer to the programming section titled "ANN-I/O
Options" on page 108 of this manual.
The LEDs are wired as illustrated in Figure 2.25. Note that the illustration depicts only connectors
P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
P1
11
1
10
ANN-I/O Module
24 VDC
nonresettable
+
-
TB1
TB2
JP7
+
-
+ 24V -
1
+ 24V -
REMOTE PWR
NON-RST
RST
2
SUPPLY SYNC
POWER
POWER
3
Figure 2.24 ANN-I/O Connection to FACP
P2
P3
21
30
31
20
ANN-BUS and power wiring are
supervised and power-limited
ANN
TB9
TB10
SLC
B+ A+ B- A-
ACS
A B
+ -
Installation
P4
40
Primary ANN-BUS
SLC
SLC
SHIELD
SLC
A
B
53