Master Programming Level
As an example, the user could quickly enter 'FLR_3_ROOM 305' as follows:
1.
2.
3.
4.
5.
EDIT CONTROL

1=MNS OVERRIDE

NO
MNS Override
Edit Control Screen #5
The MNS Override feature, when enabled, allows the ECC-50/100 to override the FACP and turn
off an active control module or prevent the control module from activating during a mass notifica-
tion event. Pressing 1 while viewing Edit Control Screen #5 will cause the display to change from
the factory default of MNS Override No to MNS Override Yes. Each press of the 1 key will cause
the display to toggle between the two options.
3.6.3 Zone Setup
Pressing 3 while viewing Programming Screen #1 will access the Zone Setup screens as illustrated
PROGRAMMING
1=AUTOPROGRAM
below:
2=POINT PROGRAM

3=ZONE SETUP

Programming Screen #2

1=ENABLE

2=DISABLE

3=ZONE 97 98 99
Enable
ZONE SETUP
1=ENABLE
Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z.
Another zone can then be enabled.
Disable
ZONE SETUP
1=ENABLE
2=DISABLE
Pressing 2 for Disable, while viewing Zone Setup Screen #1, will display the following screen:
3=ZONE 97 98 99
Zone Setup Screen #1
MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character is 9 it goes to 0.
The above increment function may be repeated with each press of the zero key.
The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field.
With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
Press the right arrow key to advance the zone field.
Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01
through Z99 may be selected to link software zones.
ZONE SETUP
Zone Setup Screen #1
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONE TO ENABLE
Z
Enable Screen
ZONE TO DISABLE
Z
Disable Screen
Programming
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9600lseMs-9600udlsMs-9600udlseMs-9600lsc