Timers - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Programming
Daylight Savings Time
TIME AND DATE
1=DAYLIGHT SAVINGS
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
Time & Date Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the
programmer to select the month that daylight savings time will begin. In this sub-screen, pressing
1 will select March, 2 will select April, and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will begin. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third
week, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select the
last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the
programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1
will select September, 2 will select October, and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will end. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third
week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the
last week of the selected month.

Timers

SYSTEM SETUP
1=TIMERS
2=NAC
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while
3=RELAYS
viewing System Setup Screen #2. The following screen will be displayed:
System Setup Screen #2
PAS (Positive Alarm Sequence) Delay
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds
3=WATERFLOW
000
for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following
Timer Screen #1
display will appear:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will
indicate the new delay time.
94
DAYLIGHT SAVINGS
1=ENABLED
YES
2=START MONTH
MAR
3=START WEEK
WEEK-2
Daylight Savings Screen #1
TIMERS
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
RANGE 0-180 SECONDS
PAS Delay Screen
DAYLIGHT SAVINGS
1=END MONTH
2=END WEEK
Daylight Savings Screen #2
TIMERS
1=AC LOSS DELAY 000
Timer Screen #2
PAS DELAY
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level
NOV
WEEK-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents