Installation of Optional Modules

4XZMF Zone Relay Module (MS-4 only)

The 4XZMF provides four zone alarm, one system alarm and one system trouble Form-C relays.
Nonpower-limited and power-limited wiring must have a minimum distance of 0.25", wire to wire.
If this module is used to drive nonpower-limited and power-limited circuits, follow the instructions
below:
1.
Skip a set of dry contacts to maintain the 0.25" required space between power-limited and
nonpower-limited circuits. The wiring of this module must follow the requirements as
specified in "Power-limited Wiring Requirements" on page 24.
2.
If this module is needed to drive power-limited and nonpower-limited relays that are next to
each other, refer to the following illustration which shows a typical connection:
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
Relay #1 through #4 will activate with
Output #1 through #4 and remain latched.
Use Disable Switch to
disconnect the relays
OR
NO
{
Relay #1
NC
C
NO
{
Relay #2
NC
C
no connection
NO
{
Relay #3
NC
C
NO
{
Relay #4
NC
C
Figure 2.14 4XZMF Zone Relay Module
1
NO
}
Relay #1
2
NC
3
C
4
NO
}
Relay #2
5
NC
6
C
7
NO
}
Relay #3
8
NC
9
C
10
NO
}
Relay #4
11
NC
12
C
13
NO
}
Alarm
14
NC
15
C
16
NO
}
Trouble
17
NC
18
C
}
power-limited circuit
}
power-limited circuit
}
nonpower-limited circuit
}
nonpower-limited circuit
Installation