11: Clear Program; 12: Program Check - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Programming
The following screen will appear when any change option is selected:
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
Re-enter the new password to accept the change. The display will return to the initial Password
Change Screen.
3.6.11 Clear Program
Pressing 2 while viewing Programming Screen #4, will select the Clear Program option. This will
PROGRAMMING
1=PASSWORD CHANGE
cause the LCD to display the following screen:
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
Pressing 1, for Whole System while viewing the Clear Program Screen #1, will clear all general
system programming options and all programmed addressable devices from the nonvolatile
memory of the FACP. This function is useful when the control panel is first installed, prior to
autoprogramming. Note that it is necessary to autoprogram after using the Clear Whole System
function.
Pressing 2, for ALL POINTS while viewing the Clear Program Screen #1, will clear all
programming related to the SLC loop and connected addressable devices.
Before executing any of the Clear commands listed above, the control panel will provide a warning
to the user by prompting with the following display:
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will
prevent programming from being cleared.
3.6.12 Program Check
The Program Check feature allows the programmer to view the zones which have been
PROGRAMMING
1=PASSWORD CHANGE
programmed to the Notification Appliance Circuits on the control panel but have not been
2=CLEAR PROGRAM
3=PROGRAM CHECK
programmed to Initiating Devices as well as other circuits with no input or output correlations.
Programming Screen #4
Pressing 3 while viewing Programming Screen #4 will cause the following screen to be displayed:
126
ENTER NEW FIVE DIGIT
PASSWORD
Enter Password Screen
VERIFY NEW PASSWORD
Password Change Screen
CLEAR PROGRAM
1=WHOLE SYSTEM
2=ALL POINTS
Clear Program Screen #1
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES
2=NO
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents