Appendix G: Ademco Contact Id Format Event Code Descriptions; G.1: Transmission Format Between Dact And Receiver; G.2: Ademco Contact Id Typical Printout - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Appendix G: Ademco Contact ID Format Event Code
This appendix describes the various Event Codes and their messages which are available for the
Ademco Contact ID Format.
G.1 Transmission Format Between DACT and Receiver
The transmission string for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC where
SSSS
18=
Q=
XYZ=
GG=
CCC=
Notes:
1.
18, which is used in the reporting structure to identify the transmission as Contact ID, is not
printed out in the alarm and trouble report.
2.
GG Group Number is fixed at '00' except for multi-building systems using the Lite-Connect
(ANN-LC) fiber card where GG indicates the node number.
3.
CCC for Zone or Point Number:
Zone Number is transmitted as '01' for zone 1 up to '99' for zone 99
Point Number is transmitted as '01' for point/address 1 up to '99' for point/address 99
G.2 Ademco Contact ID Typical Printout
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble
reports in the Ademco Contact ID Reporting Structure follows:
Time
Date
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
11:28
03/25
Notes:
1.
11 is an example of a Receiver/Line Card, showing which receiver and line card the message
was transmitted to.
2.
Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E
for New Event or R for New Restore.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Descriptions
Four digit Subscriber ID Account Code
Identifies transmission as Contact ID to the receiver at the Central Station
Event Qualifier where 1 = New Event and 3 = New Restore
Event code
Group number
Zone/Point number
Rcvr/Line ID
SSSS
QXYZ
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
11
7777
GG
CCCC
C001 - general fire alarm on zone one
E110
00
C002 - smoke detector alarm on zone two
E111
00
C003 - fault on zone three
E380
00
C009 - Zone nine disabled
E570
00
C001 - Zone one alarm restored
R110
00
C002 - smoke detector zone two restored
R111
00
C003 - zone three fault restored
R380
00
C009 - zone nine reenabled
R570
00
C006 - high temperature, zone six
E158
00
C007 - gas detected, zone seven
E151
00
182

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents