Master Programming Level
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will
indicate the new delay time.
Note that the FACP allows programming for PAS and Pre-signal timers, but a detector can only be
programmed for either PAS or Pre-signal operation. Refer to"Edit Detector" on page 68 for
programming details.
TIMER
1=PAS DELAY
000
2=PRE SIGNAL
000
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
3=WATERFLOW
000
in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no
Timer Screen #1
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.
TIMER
1=AC LOSS DELAY
The reporting of a loss of AC power to a central station can be delayed by programming the length
of the desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2
Timer Screen #2
to display the following:
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss
report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Pre-signal Delay
Waterflow Delay
AC Loss Delay
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Screen
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
AC LOSS DELAY
RANGE 00-23
AC Loss Delay Screen #2
Programming