Programming
With the preceding program settings, when the detector with address 005 is activated, zone Z98
will cause its associated control module to activate immediately, sounding the connected signaling
device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone Z001 will
cause its associated control module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both

Zone Assignment

EDIT DETECTOR
1=ZONE ASSIGNMENT
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while
00 
viewing Edit Detector Screen #4 displays the following screen:
Edit Detector Screen #4
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zone Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate
through the zones and the CLEAR key can be used to quickly clear a zone.

Noun/Adjective

EDIT DETECTOR
1=NOUN/ADJECTIVE
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
2=DESCRIPTION

detector currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will cause
Edit Detector Screen #5
the following screen to be displayed:
72
ZONE ASSIGNMENT
Z00 Z Z Z Z
Zone Assignment Screen
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen