Programming

Relays

SYSTEM SETUP
1=TIMERS
2=NAC
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two
3=RELAYS
main circuit board Form-C relays from the following screen:
System Setup Screen #2
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that
Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The
following screen will appear for each relay to be programmed:
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be
displayed:
While viewing the selected screen, press the number corresponding to the desired relay type to
program the main circuit board relay. The choice will be stored in memory and the display will
return to the Relay Type Screen which will show the programmed type choice. Press the Escape
key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining
relays.
NOTES:
1. AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the
Supervisory and/or Process Monitor type code, when activated, will automatically reset when the
corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and
deactivate when the FACP Alarm Silenced LED is illuminated.

Canadian Option

SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with
3=MNS OVERRIDE
Canadian requirements. The display will change to Canadian Opt. On. Each press of the 1 key
System Setup Screen #3
will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.
100
RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
RELAY #
1=TYPE
Relay Type Screen
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
SYSTEM SETUP
1=CANADIAN OPT.
2=WATERFLOW SIL.
3=MNS OVERRIDE
ALARM
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS-MON
Relay Screen #2
RELAY
1=MEDICAL
2=SILENCEABLE ALARM
Relay Screen #4
OFF
NO
NO
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level