Fire-Lite MS-9200UDLS Manual page 62

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Installation
Connect the ECC-50/100 panel's FACP Data Bus at TB13 to TB9 on the MS-9200UDLS FACP.
ECC-50/100
The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair of commu-
nication wires connected between the A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals
2 & 3 of the ACC-ZPMK module on the audio panel.
Figure 2.36 FACP Connection to ACC-25/50ZS(T) Series Audio Panel (Legacy)
62
to other ACS/ANN
devices
Figure 2.35 FACP Connection to ECC-50/100 Series Audio Panel
+ -
ACC-ZPMK
on ACC-25/50ZS(T) Series
A (+)
TB5
TB6
TB8
NO NC C
NC NO C
Xmt Rcv Dtr Gnd
A
In+ In- Out+ Out-
MS-9200UDLS
A
B
ANN
ACS
+
-
TB8
TB9
TB10
ACS
OUT+ IN+ OUT- IN-
MS-9200UDLS
ON
S1
TENS ONES
O N
1 2 3 4 5 6 7 8
S3
S2
B (-)
Primary ANN-BUS
TB9
TB10
+
-
B+ A+ B- A- A B
A
B
B
Slc Slc Slc Slc Shield
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Automatic Audio Panel Control
SLC
SLC
SLC
SHIELD
SLC
B+ A+ B- A-
A
B