Fire-Lite MS-9200UDLS Manual page 171

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2.
Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of 4XTMF module
and circuit.
3.
Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory relay.
4.
Refer to "4XTMF Transmitter Module Installation" on page 39 for detailed information.
Polarities shown in alarm condition
Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
NFPA Standard-Specific Requirements
Municipal Box
Circuit
Gamewell Model M34-56 Local
Nonpower-limited
-
+
4XTMF
FIRE
+
-
Energy Municipal Box
171